Quick Summary
Pressure transducer sensitivity is the amount of electrical output a sensor produces for each unit of applied pressure, while resolution is the smallest pressure change a system can reliably detect. Sensitivity sets how large the signal is, and noise and electronics set how finely it can be read. Matching both to the working pressure range usually decides the fit.
Anyone reading a datasheet for a pressure transducer meets millivolts per volt, a full-scale range in psi and a list of accuracy terms, and it is not obvious which number limits a real measurement. Pressure transducer sensitivity and resolution answer much of that question. Sensitivity describes how much signal a pressure change creates, and resolution describes how small a change the whole system could possibly reveal.
The two terms are often mixed up, and mixing them up can lead to a transducer that is over-specified for one job or unable to see the pressure changes another job depends on.

What Pressure Transducer Sensitivity Means
A strain gauge transducer works by letting pressure bend a thin diaphragm. Strain gauges bonded to that diaphragm change their electrical resistance very slightly, and a bridge circuit turns the change into a small voltage that rises and falls with pressure.
Sensitivity is the change in that output divided by the change in pressure. It is written as millivolts per psi, or as millivolts per volt of excitation for each psi. Datasheets often give the full-scale output instead, such as 2 mV/V at the top of the range, and dividing that figure by the range gives the same information.
A lever offers a helpful comparison. A longer lever moves farther for the same push, and a more sensitive transducer produces more signal for the same pressure change. A larger signal could potentially make small pressure changes easier to pick out from electrical noise.
What Resolution Means in a Pressure Sensor
Resolution is the smallest change in pressure that produces a distinguishable change in the reading. It describes the limit of the measurement, not the strength of the signal.
With an analog output, resolution is possibly limited less by the sensor than by electrical noise, because any change smaller than the noise gets lost in it. With a digital output, bit depth also matters. A 12-bit converter divides the measurement span into 4,096 steps, and a 16-bit converter divides it into 65,536.
A ruler shows the idea. Markings every millimeter let you separate two close lengths, while markings every inch do not. Finer markings only help, though, if the object being measured holds still, which is why noise plays the same role in a pressure reading. The readout instrument counts as well, since a meter with coarse steps can hide detail the sensor is already delivering.
How Sensitivity and Resolution Differ
Sensitivity is a slope: signal produced per unit of pressure. Resolution is a limit: the smallest step that can be told apart from the background. They are related through noise, and a rough rule of thumb is that resolution in pressure units equals the noise level divided by the sensitivity.
That rule explains why a more sensitive transducer could potentially resolve smaller pressure changes when the noise stays the same. Each psi simply produces more signal to stand above it.
The two numbers do not move in lockstep, though. Sensitivity belongs mostly to the sensor, while resolution belongs to the whole measurement chain, including wiring, amplifier and converter. A transducer datasheet alone rarely settles what resolution a finished system will deliver.
A Worked Example With Simple Numbers
Consider an illustrative transducer with a 0 to 100 psi range, a 2 mV/V output and 10 V of excitation. Full-scale output is 20 mV, so sensitivity works out to 0.2 mV for every psi.
Suppose the full measurement chain shows 0.02 mV of noise. Dividing 0.02 mV by 0.2 mV per psi gives roughly 0.1 psi, so changes near that size could possibly be told apart. A 16-bit converter spread across 20 mV would step in increments near 0.0003 mV, far finer than the noise, so noise rather than the converter sets the limit in this case.
Now keep the same 2 mV/V output but choose a 0 to 10 psi range. The same 20 mV now covers only 10 psi, giving 2 mV per psi, and the same noise corresponds to about 0.01 psi. In absolute terms that is ten times finer, yet both cases come to 0.1 percent of full scale, which is one reason resolution is often quoted as a percentage of span.
These figures are illustrations, not specifications of any Stellar Technology product. Real values depend on the model, the excitation and the electronics behind it.
Sensitivity, Accuracy and Stability Are Different Things
Accuracy describes how close a reading comes to the true pressure, and it combines several errors, including nonlinearity, hysteresis and repeatability. Stability describes how well the output holds steady over time and across temperature.
A transducer can be highly sensitive and still inaccurate if its output curve bends or drifts. Fine resolution does not guarantee accuracy either, because a reading that changes in tiny steps can still sit off by a constant offset. Reading a datasheet well means checking each term on its own rather than assuming one implies the others.
What Affects Sensitivity and Resolution in a Working System
Several practical factors could shift both numbers once a transducer leaves the bench:
- Excitation voltage. Output in millivolts scales with excitation, so a higher supply could potentially raise the signal, as long as it stays within the sensor’s rated limits.
- Wiring and shielding. Long, unshielded cable runs can pick up electrical interference that raises the noise floor and coarsens resolution.
- Signal conditioning. Amplifier gain and amplifier noise matter, which is why pressure transducers and transmitters are chosen differently: a transmitter adds conditioning inside the unit and outputs a larger voltage or current signal.
- Pressure range. A range close to the working pressure leaves more of the output span in use, though it should still leave margin for pressure spikes.
- Shifts in zero and output with temperature could blur small changes if the transducer is not compensated for them.
Matching a Transducer to the Application
Start with two numbers: the smallest pressure change that matters and the highest pressure the system could see, spikes included. Those two figures frame the range, the sensitivity and the resolution an application needs. Output type, media and operating environment then narrow the choice.
Stellar Technology manufactures pressure transducers and transmitters in Amherst, NY, and its quality system is certified to ISO 9001:2015 and AS9100D. Product approvals such as CSA or ATEX apply only to the series named on each approval, so scope is worth confirming for the exact model under consideration.
Standard series cover different output types and environments, from general transducers and transmitters to a space-rated pressure transducer. When no standard model offers the range or sensitivity an application calls for, a modified-standard or custom design may be possible.
FAQs
How is the sensitivity of a sensor defined?
A sensor’s sensitivity is its output change divided by the change in whatever it measures, which for a pressure transducer means output per unit of pressure. On a datasheet the figure usually appears as millivolts per psi, or as millivolts per volt of excitation per psi, which is why the excitation must be stated alongside it. Two sensors can only be compared fairly when both figures use the same units and the same excitation, so check that before ranking one above another.
What is the sensitivity of a strain gauge?
The sensitivity of a strain gauge is its gauge factor, meaning how much its resistance changes in proportion to the strain it feels. Metal foil gauges commonly sit near 2, while semiconductor gauges can be much higher but tend to react more strongly to temperature. When a design needs a large signal from a very small deflection, gauge type could be a deciding factor, usually alongside the temperature compensation it requires.
What is a strain gauge-based pressure transducer?
A strain gauge-based pressure transducer is a pressure sensor whose strain gauges, bonded to or formed on a diaphragm, are wired as a bridge circuit, so a given pressure produces a proportional voltage. Because that output is only millivolts, it helps to plan wiring, excitation and conditioning together with the sensor rather than choosing the sensor alone.
What are the two types of pressure transducers?
A common split is by output: analog transducers give a millivolt, voltage or current signal, while digital versions convert the signal inside the unit and report a number over a serial link. Another split is by reference, as gauge, absolute or differential. Analog output often suits wiring into existing instruments, whereas digital output could simplify data handling in some systems.
Engineering and custom applications are our specialty, so contact Stellar Technology to talk through the sensitivity, range and resolution your application calls for.